Steve Taylor Steve Taylor
0 Course Enrolled • 0 Course CompletedBiography
High Pass-Rate Valid CDCS Test Review | 100% Free CDCS Test Pass4sure
BONUS!!! Download part of Actual4Labs CDCS dumps for free: https://drive.google.com/open?id=10YRVbI75yDGs-Svyrj1XrbL7S67IYP_U
It is worth mentioning that, the simulation test is available in our software version. With the simulation test, all of our customers will get accustomed to the CDCS exam easily, and get rid of bad habits, which may influence your performance in the real CDCS exam. In addition, the mode of CDCS learning guide questions and answers is the most effective for you to remember the key points. During your practice process, the CDCS Test Questions would be absorbed, which is time-saving and high-efficient. Considerate 24/7 service shows our attitudes, we always consider our candidates’ benefits and we guarantee that our CDCS test questions are the most excellent path for you to pass the exam.
EXIN CDCS Exam Syllabus Topics:
| Topic | Details |
|---|---|
| Topic 1 |
|
| Topic 2 |
|
| Topic 3 |
|
CDCS latest study torrent & CDCS practice download pdf
If you want to improve your career prospects, obtaining EXIN EPI Certified Data Centre Specialist, CDCS exam certificate is a great way for you. EXIN EPI Certified Data Centre Specialist certificate will help you land a job in the industry. After passing the EXIN EPI Certified Data Centre Specialist you can increase your earning potential. This is because employers are ready to pay more for candidates who have passed the EXIN CDCS Certification test. Success in the CDCS exam can impact your promotion. If you are already an employee you can promote yourself to the highest level after passing the EXIN CDCS test.
EXIN EPI Certified Data Centre Specialist Sample Questions (Q101-Q106):
NEW QUESTION # 101
You are working on the design of a new facility. The electrical riser of the building with high current power is located close to the area where sensitive IT equipment in the computer room will be located.
What should you recommend to reduce the amount of EMF coming from the electrical riser?
- A. Install three-phase power cabling based on three individual core wires
- B. Install single-phase power cabling
- C. Install bus bar trunking
- D. Install three-phase power cabling based on a combined cable (e.g. XLPE etc.)
Answer: D
Explanation:
To reduce Electromagnetic Fields (EMF) emanating from the electrical riser near sensitive IT equipment, three-phase power cabling in a combined cable (such as XLPE) is effective. Combined cabling helps reduce EMF by keeping the conductors tightly packed, which minimizes magnetic fields generated by current flow.
Cables like XLPE (cross-linked polyethylene) also offer better insulation, which helps mitigate EMF interference with nearby IT equipment.
Detailed Explanation:
Using a combined three-phase cable reduces EMF because the magnetic fields generated by each phase tend to cancel each other out when in close proximity. This arrangement helps reduce the overall magnetic field strength. In addition, XLPE and similar materials provide good insulation, making them a preferred choice for reducing EMF emissions around sensitive equipment.
EPI Data Center Specialist References:
EPI data center best practices recommend mitigating EMF interference through combined cabling arrangements, especially near areas where sensitive IT equipment is located. Reducing EMF is crucial to maintaining equipment reliability and ensuring compliance with safety standards.
NEW QUESTION # 102
You are allowed to use a calculator for this question.
A computer room has a net volume of approximately 2,500 m³ / 88,287 ft³.
The temperature is 20 °C / 68 °F.
The required design concentration is 7%.
The S-Factor is 0.1359 (metric) / 1.885 (imperial).
Calculate the amount of gas required for this computer room based on FM200. What is the correct weight?
- A. Approximately 1,640 kg / 3,600 lbs
- B. Approximately 820 kg / 1,800 lbs
- C. Approximately 1,390 kg / 3,000 lbs
- D. Approximately 410 kg / 900 lbs
Answer: B
Explanation:
The amount of FM200 gas required can be calculated using the formula:
Weight of Gas=Net Volume×Design Concentration×S-Factor ext{Weight of Gas} = ext{Net Volume}
imes ext{Design Concentration} imes ext{S-Factor}
Weight of Gas=Net Volume×Design Concentration×S-Factor
Using metric units:
* Net Volume: 2,500 m³
* Design Concentration: 7% (or 0.07)
* S-Factor: 0.1359
Calculation:
2,500 m3×0.07×0.1359=821.325 kg2,500 , ext{m}